E2618-CL2

Chlorine Transmitter

Features
  • Stable long-life electochemical sensor
  • Range 0...10 ppm Cl2
  • Resoluton 0,1 ppm Cl2
  • 2 × 4-20 mA or 0-10 V, RS485
Description

Chlorine transmitter E2618-Cl2 is a member of new PluraSens® family of multifunctional measurement instruments.

Applications include swimming pools and spas, wastewarer treatment plants and other confined spaces, where potentially toxic concentration of chlorine  can accumulate.

The instrument utilises a fully calibrated and temperature compensated electrochemical gas sensor with excellent repeatability, stability and long lifetime.

Two analog outputs and RS485 digital interface with industry standard Modbus RTU protocol can be used to connect the detector to safety or building automation systems.


Technical data
Calibration chlorine Cl2
Sensor type electrochemical
Sampling method diffusion
Detection range 0...10 ppm Cl2
Resolution 0,1 ppm Cl2
Sensor lifetime 2 years
Power supply 12...36 VDC (default)
24 VAC as option
Digital interface RS485, Modbus RTU protocol
Analog outputs 2 × 4-20 mA / 0-10 V, user settable
Enclosure grey ABS plastic, wall mount, IP65
Dimensions H82 × W80 × D55 mm
Operating conditions -20...+50 °C, 15...90 %RH