E2670-NO2

Flameproof Nitrogen Dioxide Detector

Features
  • Suitable for ATEX Zones 2 and 22
  • Stable long-life electrochemical sensor
  • Range 0...20 or 0...200 ppm NO2
  • Resolution 0,1 ppm or 1 ppm NO2
  • Two SPST relays option
  • 2 × 4-20 mA or 0-10 V, RS485
Description

E2670 series is a new line of flameproof detectors-transmitters intended for use in ATEX Zones 2 and 22.

E2670 series devices are based on PluraSens® multifunctional platform.

Nitrogen dioxide detector-transmitter E2670-NO2 utilises a fully calibrated and temperature compensated electrochemical gas sensor with excellent repeatability, stability and long lifetime.

Two relays with closing contact (optional) may be used for remote signalling or concentration control. Two alarm set-points are user settable.

Two analog outputs and RS485 digital interface with industry standard Modbus RTU protocol can be used to connect the detector to safety or building automation systems.


Technical data
Calibration nitrogen dioxide NO2
Sensor type electrochemical
Sampling method diffusion
Detection range 0...20 ppm NO2
0...200 ppm NO2
Resolution 0,1 ppm NO2 for 20 ppm range
1 ppm NO2 for 200 ppm range
Sensor lifetime > 2 years
Power supply 12...36 VDC (default),
24 VAC or 230 VAC as options
Digital interface RS485, Modbus RTU protocol
Analog outputs 2 × 4-20 mA / 0-10 V, user settable
Output relays (option) 2 × SPST relays (closing contact),
250 VAC / 30 VDC, 5 A max
Default alarm set-points 3 ppm / 6 ppm NO2
Enclosure die-cast aluminium, wall mount, IP65
Dimensions H155 × W145 × D110 mm
Operating conditions -20...+50 °C, 15...90 %RH
safe areas and ATEX Zones 2 and 22

Similar Products


TXgard+ - Toxic and oxygen gas detector
TXgard+ - Toxic and oxygen gas detector
  • Calibration can be performed locally without the need for hot work permits
  • Local display and magnetic key enable calibration without opening the junction box
  • 4...20mA signal is provided
  • Optional alarm and fault relays are available

TXgard-IS+ - Toxic and oxygen gas detector
TXgard-IS+ - Toxic and oxygen gas detector
  • Wide choice of sensors available
  • Local calibration option
  • 2-wire 4-20mA
  • Operating range: -20...+55 °C, 15...90% RH
  • ABS plastic housing, IP65

E2608-NO2 - Nitrogen Dioxide Detector
E2608-NO2 - Nitrogen Dioxide Detector
  • Stable long-life electrochemical sensor
  • Range 0...20 or 0...200 ppm NO2
  • Resolution 0,1 ppm or 1 ppm NO2
  • Two SPST relays
  • 2 × 4-20 mA or 0-10 V, RS485

Xsafe - Gas detector for non-hazardous areas
Xsafe - Gas detector for non-hazardous areas
  • Aluminium junction box
  • Working range: -40...+80°C, 0-99% RH
  • 3-wire 4-20 mA
  • IP65
  • Deploy in non-hazardous environment