E2670-PID

Flameproof Solvent Vapors Detector

Features
  • Suitable for ATEX Zones 2 and 22
  • Highly sensitive Photo Ionization Detector
  • Range 0...40 or 0...200 ppm isobutylene
  • Resolution 0,01 ppm or 1 ppm isobutylene
  • Two SPST relays option
  • 2 × 4-20 mA or 0-10 V, RS485
Description

E2670 series is a new line of flameproof detectors-transmitters intended for use in ATEX Zones 2 and 22.

E2670 series devices are based on PluraSens® multifunctional platform.

Solvent vapors transmitter E2670-PID utilises highly sensitive photoionization detectors (PID) with extremely low minimal detection levels. The transmitter exhibits sensitivity to compounds with ionization potential less than 10.6 eV, i.e. to most solvent vapors.

Two relays with closing contact (optional) may be used for remote signalling or concentration control. Two alarm set-points are user settable.

Two analog outputs and RS485 digital interface with industry standard Modbus RTU protocol can be used to connect the detector to safety or building automation systems.


Technical data
Detected vapors acetone, ethanol, toluene, xylene etc
Default calibration isobutylene
Sensor type Photo Ionization Detector
Sampling method diffusion
Detection range 0...40 ppm isobutylene
0...200 ppm isobutylene
Resolution 0,01 ppm C4H8 for 40 ppm range
1 ppm C4H8 for 200 ppm range
Sensor lifetime 5 years
Power supply 12...36 VDC (default),
24 VAC or 230 VAC as options
Digital interface RS485, Modbus RTU protocol
Analog outputs 2 × 4-20 mA / 0-10 V, user settable
Output relays (option) 2 × SPST relays (closing contact),
250 VAC / 30 VDC, 5 A max
Enclosure die-cast aluminium, wall mount, IP65
Dimensions H155 × W145 × D110 mm
Operating conditions -40...+65 °C, 0…95 %RH
safe areas and ATEX Zones 2 and 22