E2638-CL2

Chlorine Detector

Features
  • Stable long-life electochemical sensor
  • Range 0...10 ppm Cl2
  • Resoluton 0,1 ppm Cl2
  • Two SPST relays option
  • 2 × 4-20 mA or 0-10 V, RS485
Description

Chlorine detector-transmitter E2638-Cl2 is a member of new PluraSens® family of multifunctional measurement instruments.

Applications include swimming pools and spas, wastewater treatment plants and other areas, where potentially toxic concentration of chlorine can accumulate.

The instrument utilises a fully calibrated and temperature compensated electrochemical gas sensor with excellent repeatability, stability and long lifetime.

Two relays with closing contact (optional) may be used for remote signalling or concentration control. Two alarm set-points are user settable.

Two analog outputs and RS485 digital interface with industry standard Modbus RTU protocol can be used to connect the detector to safety or building automation systems.


Technical data
Calibration chlorine Cl2
Sensor type electrochemical
Sampling method diffusion
Detection range 0...10 ppm Cl2
Resolution 0,1 ppm Cl2
Sensor lifetime 2 years
Power supply 12...36 VDC (default),
24 VAC or 230 VAC as options
Digital interface RS485, Modbus RTU protocol
Analog outputs 2 × 4-20 mA / 0-10 V, user settable
Output relays (option) 2 × SPST relays (closing contact),
250 VAC / 30 VDC, 5 A max
Default alarm set-points 0,5 ppm / 1 ppm Cl2
Enclosure grey ABS plastic, wall mount, IP65
Dimensions H90 × W145 × D55 mm
Operating conditions -20...+50 °C, 15...90 %RH