- Stable long-life electrochemical sensor
- Range 0...10 ppm NO2
- Resolution 0,1 ppm NO2
- Two SPST relays
- UART digital interface
Nitrogen dioxide detector E2630-NO2 is an easy-to-use instrument intended for underground parkings, boiler houses, laboratories, industrial premises and other confined spaces, where potentially toxic concentration of nitrogen dioxide can accumulate.
The instrument utilises a fully calibrated and temperature compensated electrochemical gas sensor with excellent repeatability, stability and long lifetime.
Two relays with switch-over contact may be used for remote signalling or ventilation control. Flashing LED and internal buzzer give visual and sound alarms.
Calibration | nitrogen dioxide NO2 |
Sensor type | electrochemical |
Sampling method | diffusion |
Detection range | 0...10 ppm NO2 |
Resolution | 0,1 ppm NO2 |
Sensor lifetime | > 2 years |
Poswer supply | 24 VDC/AC ±20% (default) |
or 230 VAC (optional) | |
Digital interface | UART |
Output relays | 2 x SPDT relays (switch-over contact) |
250 VAC / 30 VDC, 5 A max | |
Alarms | blinking LED, buzzer 85 dB |
Default alarm set-points | 3 ppm / 6 ppm NO2 |
Enclosure | grey ABS plastic, wall mount, IP65 |
Dimensions | H90 × W145 × D55 mm |
Operating conditions | -30…+50 °C, 15...90 %RH (non-condensing) |