- Simultaneous CO and combustible gases monitoring
- RS485 Modbus RTU digital interface
- Two analog outputs 4-20 mA / 0-10 V
- Easy-to-install IP65 protected enclosure
- Attached or remote sensor
- Two SPST relays option
- Acoustic alarm option
E2660-CO-LEL detector-transmitter is an easy-to-use instrument intended for simultaneous monitoring of carbon monoxide, hydrogen, methane, acetylene, propane and butane concentration.
The device may be used in underground parkings, boiler houses, battery charging rooms, energy storages and other confined spaces, where potentially toxic concentration of carbon monoxide and combustible gases can accumulate.
The instrument utilizes novel fully calibrated and temperature compensated gas sensors with excellent repeatability, stability, and long lifetime.
Two analog outputs and RS485 digital interface with industry standard Modbus RTU protocol can be used to connect the transmitter to safety or building automation systems.
Sensors type | Electrochemical cell |
metal-oxide semiconductor (MOS) | |
pellistor (catalytic bead) | |
Sampling method | Diffusion |
Detection ranges | 0...300 ppm / 0...1000 ppm CO |
0...100% LEL | |
Resolution | 1 ppm vol CO |
0,1 / 1% LEL | |
Sensor lifetime | Pellistor - >3 years |
MOS - >5 years | |
Electrochemical - >10 years | |
Calibration interval | 6 months (pellistor) |
12 months (electrochemical and MOS) | |
Power supply | 12...36 VDC (default), |
24 VAC or 230 VAC as options | |
Analog outputs | two 4-20 mA / 0-10 V (user settable) |
Enclosure | grey ABS plastic, IP65 |
Dimensions | H90 × W145 × D50 mm |
Operating conditions | -20...+50 °C, 15...90 %RH |