E2638-NH3-P

Ammonia Detector

Features
  • Stable long-life pellistor sensor
  • Range 0...15% vol. (0…100% LEL)
  • Resolution 0.1% vol. or 1% LEL
  • Two SPST relays option
  • 2 × 4-20 mA or 0-10 V, RS485
  • Attached or remote sensor
  • LCD indicator option
  • Easy to install IP65 enclosure
Description

Ammonia transmitter E2618-NH3-P is a member of the PluraSens® family of multifunctional measurement instruments.

One of the most common applications is detection of explosive Ammonia concentrations in refrigeration machinery rooms.

The instrument utilizes a fully calibrated and temperature compensated pellistor (catalytic) gas sensor with excellent repeatability, stability and long lifetime.

Two relays with closing contact (optional) may be used for remote signaling or concentration control. Two alarm set-points are user settable.

Two analog outputs and RS485 digital interface with industry standard Modbus RTU protocol can be used to connect the detector to safety or building automation systems.


Technical data
Calibration Ammonia NH3
Sensor type Pellistor (catalytic bead)
Sampling method Diffusion
Detection range 0...15% vol. (0…100% LEL)
Resolution 0.1% vol. or 1% LEL
Response time T90 ≤10 s
Sensor lifetime > 3 years
Power supply 12...36 VDC (default),
24 VAC or 230 VAC as options
Digital interface RS485, Modbus RTU protocol
Analog outputs 2 × 4-20 mA / 0-10 V, user settable
Output relays (option) 2 × SPST relays (closing contact),
250 VAC / 30 VDC, 5 A max
Enclosure grey ABS plastic, wall mount, IP65
Dimensions H90 × W145 × D55 mm
Operating conditions -10...+50 °C, 0...95% RH

Similar Products


Xgard - Flammable, toxic or oxygen gas detector
Xgard - Flammable, toxic or oxygen gas detector
  • Aluminium, stainless steel or glass-reinforced nylon body
  • Operating range: -40...+80°C, 0-99% RH (non-condensing)
  • 2- wire 4-20mA or 3- wire mV bridge
  • IP54 to IP65
  • Deploy in hazardous environment certified

Gasman - Personal single gas detector
Gasman - Personal single gas detector
  • Available for flammable gas, oxygen and toxic gases
  • Rechargeable versions for all gas types
  • Non rechargeable for oxygen and toxic gases
  • Loud 95dBA audible alarm

Tetra - Personal multigas monitor
Tetra - Personal multigas monitor
  • Battery non- or rechargeable options
  • Graphic LCD for clear view
  • Single button operation
  • Loud 94dBA audible alarm
  • Shock and vibration resistant, IP 65

TXgard+ - Toxic and oxygen gas detector
TXgard+ - Toxic and oxygen gas detector
  • Calibration can be performed locally without the need for hot work permits
  • Local display and magnetic key enable calibration without opening the junction box
  • 4...20mA signal is provided
  • Optional alarm and fault relays are available

TXgard-IS+ - Toxic and oxygen gas detector
TXgard-IS+ - Toxic and oxygen gas detector
  • Wide choice of sensors available
  • Local calibration option
  • 2-wire 4-20mA
  • Operating range: -20...+55 °C, 15...90% RH
  • ABS plastic housing, IP65

E2608-NH3-E - Ammonia Detector
E2608-NH3-E - Ammonia Detector
  • Stable long-life electrochemical sensor
  • Range 0...100 / 0...300 / 0...1000 / 0...5 000 ppm NH3
  • Resolution 1 ppm NH3
  • Two SPST relays
  • 2 × 4-20 mA or 0-10 V, RS485

Tetra-3 - Personal four-gas monitor
Tetra-3 - Personal four-gas monitor
  • Top display, single button operation
  • Water and dust resistant up to IP67
  • 95dB audible, vibration and visual alarms
  • Li-ion battery for over 14 h operation
  • Data logging (>12000 logs)

E2618-NH3-E - Ammonia Transmitter
E2618-NH3-E - Ammonia Transmitter
  • Stable long-life electrochemical sensor
  • Range 0...100 / 0...300 / 0...1000 / 0...5 000 ppm NH3
  • Resolution 1 ppm NH3
  • 2 × 4-20 mA or 0-10 V, RS485

Xsafe - Gas detector for non-hazardous areas
Xsafe - Gas detector for non-hazardous areas
  • Aluminium junction box
  • Working range: -40...+80°C, 0-99% RH
  • 3-wire 4-20 mA
  • IP65
  • Deploy in non-hazardous environment

E2638-NH3-E - Ammonia Detector
E2638-NH3-E - Ammonia Detector
  • Stable long-life electrochemical sensor
  • Range 0...100 / 0...300 / 0...1000 / 0...5 000 ppm NH3
  • Resolution 1 ppm NH3
  • Two SPST relays option
  • 2 × 4-20 mA or 0-10 V, RS485

E2648-NH3-E - Ammonia Detector
E2648-NH3-E - Ammonia Detector
  • Stable long-life electrochemical sensor
  • Range 0...100 / 0...300 / 0...1000 / 0...5 000 ppm NH3
  • Resolution 1 ppm NH3
  • Two SPST relays option
  • 2 × 4-20 mA or 0-10 V, RS485

E2608-NH3-P - Ammonia Detector
E2608-NH3-P - Ammonia Detector
  • Stable long-life pellistor gas sensor
  • Range 0...15% vol. (0…100% LEL)
  • Resolution 0.1% vol. or 1% LEL
  • Two SPST relays
  • 2 × 4-20 mA or 0-10 V, RS485
  • Wall-mount or duct-mount version
  • Attached or remote sensor

E2618-NH3-P - Ammonia Detector
E2618-NH3-P - Ammonia Detector
  • Stable long-life pellistor gas sensor
  • Range 0...15% vol. (0…100% LEL)
  • Resolution 0.1% vol. or 1% LEL
  • Wall mount or duct mount version
  • Attached or remote sensor
  • 2 × 4-20 mA or 0-10 V, RS485

E2648-NH3-P - Ammonia Detector
E2648-NH3-P - Ammonia Detector
  • Stable long-life pellistor sensor
  • Range 0...15% vol. (0…100% LEL)
  • Resolution 0.1% vol. or 1% LEL
  • Two SPST relays option
  • 2 × 4-20 mA or 0-10 V, RS485
  • Attached or remote sensor
  • Industrial IP66 wall mount housing

E2670-NH3-E - Flameproof Ammonia Detector
E2670-NH3-E - Flameproof Ammonia Detector
  • Suitable for ATEX Zones 2 and 22
  • Stable long-life electrochemical sensor
  • Range 0...100 / 0...300 / 0...1000 / 0...5 000 ppm NH3
  • Resolution 1 ppm NH3
  • Two SPST relays option
  • 2 × 4-20 mA or 0-10 V, RS485

E2670-NH3-P - Flameproof Ammonia Detector
E2670-NH3-P - Flameproof Ammonia Detector
  • Suitable for ATEX Zones 2 and 22
  • Stable long-life pellistor (catalytic bead) sensor
  • Range 0...15% vol. (0…100% LEL)
  • Resolution 0.1% vol. or 1% LEL
  • Two SPST relays option
  • 2 × 4-20 mA or 0-10 V, RS485
  • Wall mount flameproof metal enclosure